Fire Safety Gas Shut-off Valves
The Model 110-G Fire Safety Gas Shut-off Valve is used in fuel gas piping systems to provide automatic shut off of fuel gas flow in the event of a fire.
Application
The Model 110-G may be used in any gas flow application by locating the valve in a horizontal pipe run where the gas supply enters the building. Install the trip wire with the fusible link located in the area to be monitored for excessive temperature.Overview
The valve is held open by a stretched wire containing a fusible link. When the temperature rises above 165° F, the link will melt and the tension of the internal spring closes the valve.Features
The Model 110-G Fire Safety Gas Shutoff Valve is used in fuel gas piping systems to provide automatic shutoff of fuel gas flow in the event of a fire. Valve operation is fully mechanical and independent of the electrical power supply. The emergency fuel line shut-off is mandated by many codes. The Model 110-G may be used in any gas flow application by locating the valve in a horizontal pipe run where the gas supply enters the building. Install the trip wire with the fusible link located in the area to be monitored for excessive temperature.
Operation: The valve is held open by a stretched wire containing a fusible link. When the temperature rises above 165° F, the link will melt and the tension of the internal spring closes the valve.
Testing: As with any piece of safety equipment, the gas shutoff valve should be tested upon completion of installation and regularly thereafter to ensure that it will close in the event of excessive temperature at the fusible link. Ideally, the link would be heated with a small flame until the link melted. The valve should snap closed immediately. If the valve does not close properly, the wire should be checked for freedom of movement, and the mechanism of the valve should be checked for free operation.
Specification
Furnish and install, as shown in the gas supply line, a quick closing, spring loaded fire safety gas shut-off valve with fusible element which melts at 165º F allowing the valve to close tightly. The fire safety gas shut-off valve shall be a Preferred Utilities Mfg. Corp., Danbury, CT, Model 110-G.DOCUMENTS & DOWNLOADS
| Fire Safety Gas Shut-off Valve - Catalog Cutsheet Fire Safety Gas Shut-off Valve - Datasheet.pdf | |
| Fire Safety Gas Shut-off Valve Installation Manual form 337 FOR GAS.pdf |
RELATED PRODUCTS
- Anti Syphon Valves
- Back Pressure Regulating Valves, Model BQ
- Back Pressure Regulating Valves, Model V
- Breather Caps
- Double Poppet Foot Valves
- Duplex Oil Strainers
- Foot Valve Extractor Fitting
- Fusomatic Electric Cut-Off Switch
- Fusomatic Globe / Gate Valves
- Ground Level Spill Containers
- Horizontal Spill Containers
- Oil Lever Gate Valves
- Oil Thermometer
- Overfill Prevention Valves
- Relief Valves
- Sidewalk Boxes
- Simplex Oil Strainers
- Single Poppet Foot Valves
- Storage Tank Monitor Access Manhole
- Tank Selector Valves
- Tank Vent Bricks
- Vacuum Breaker Valves
- Vent Protectors
- Watertight Flush Fill Caps
- Watertight Locking Fill Caps
- Pressure Reducing Valves
- Sidewalk Spill Container