Liquid Level Switch
The Model PLS Liquid Level Switch provides up to six independent liquid level switches on one sealed probe up to 72" in length. Magnetic reed switches are encapsulated in the sealed brass probe where they are protected from liquid and vapors.
Application
The Model PLS Level Switch may be used with any clean, low viscosity, non-adhering fluid compatible with brass, solder, epoxy and Buna-N. It is commonly used on fuel oil day tanks to control the addition of oil from remote pumps, and to alarm high and low levels. Other applications include pressurized or vented tanks for water, hydraulic fluid, lubricating oils or distillate fuels. Insert the unit vertically and then thread it into a 1 ¼" NPT half coupling on the tank shell. The wiring enclosure is not designed to be submerged. A suitable protective enclosure for access such as the Preferred Sidewalk Box Model 13071 should be provided when installing underground.Overview
The Model PLS Level Switch provides up to six independent liquid level switches on one sealed probe up to 72" in length. Magnetic reed switches are encapsulated in the sealed brass probe where they are protected from liquid and vapors. Buna-N floats, containing magnets, slide on the outside of the brass probe. A rising liquid level causes each float to rise to its upper travel stop position where it actuates a switch. Any switch may be specified “open” or “closed” with the float at its lower stop position.Features
Fluid Temperature: 180° F Maximum
Fluid Specific Gravity: 0.5 Minimum
Fluid Pressure: 150 PSI Maximum
Electrical: 100W at 120 VAC Resistive 8VAC Relay Coil Pilot Duty
Switch Action: Can Be N.O. or N.C.
Housing: Cast Aluminum, UL Listed
Wetted Parts: Brass Probe And Buna-N Float
- Custom Fabricated Up To 72" In Length
- May Be Used With Any Clean, Low, Viscosity, Non-Adhering Fluid
- Switches May Be Specified "Open" Or "Closed"
Specification
The tank level control shall be Model PLS-XX-Y (XX" long with Y switches) as manufactured by Preferred Utilities Mfg. Corp. Danbury, CT. Control shall be float operated, installed through and threaded into a single 1 ¼" tapping on the top of the tank, shall be suitable for pressures up to 150 psig and temperatures up to 180˚F and shall be entirely of nonferrous material with __ switches each rated at 100 Watts. Mounting: 1¼" NPT Coupling