How to scale the Precision Digital display in the Spill-Fill boxes.

FILED UNDER: PU Panel, Spill Container

Symptom

The Precision Digital PD6604-LNN used in the spill-fill boxes (3/2024) comes factory programed such that 4 to 20 mA reads 0 to 100 gal.
To change the '100' follow the steps below.

Steps to Troubleshoot

Resolution


To program the scale on this Precision Digital display
• Hit MENU Go to SETUP.
• Hit the ENTER (F3) button eleven times (11X) … until the screen displays
 o SCALE
 o DISP 2.
• Hit ENTER one more time … you should see
 o DSP2
 o +00,100.00
• Hit F1 three times to move the blinking cursor to the 1 in 100
• Hit F2 to change the 1 to a 2 … again to change the 2 to a 3 ... and so on.
• Hit F1 to move the blinking cursor to the first 0 in 100.
• Hit F2 to change the 0 to a 1.
• Hit F1 to move the blinking cursor to the second 0 in 100.
• Hit F2 to change the 0 to a 1.
• Hit F3 to save and exit.

If you need to change where the decimal point in the 100.00 is ...
• Go to SETUP
 o SETUP
 o INPUT
• Hit F1 three times (3X)to get
  o SETUP
 o DISPLAY
• Hit ENTER (F3) TO GET
 o DISPLAY
 o UNITS
• Hit F1 TO GET
 o DISPLAY
 o DECPT (Decimal Point)
• Hit ENTER (F3) and the display will show the number of decimal points, e.g. 22222222, 333333333.
• Hit F2 to change the number ... 00000000 thru 77777777. Most probablyy want to choose 00000000 or 11111111.